   Application
Direct indication of flows in systems.

   The FLOMETER offers an accurate and convenient indication of flow rates in heating, ventilation, air conditioning and cooling systems. Due to the compact design of the FLOMETER, the installation of a flow rate indicator is possible, even at most limited space. The particular connection is suitable for a direct and economic fit to components with eurocone adaptors.
   Installed on heating manifolds or on a valve, the FLOMETER forms an economical extension of the function with big benefits. For example, each throttle valve in addition with a FLOMETER turns into a multi function valve for the balancing and the indication of flow rates. With the FLOMETER, any qualified fitter can read the appropriate flow rate easily on site, without any additional measuring device or special training.

   Installation
   The valve can be installed in a horizontal, vertical or inclined position. Care should be taken in order to ensure that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float with countersprings.    The flow rate is displayed on a calibrated scale by an integrated flowmeter. The reading position is the bottom line of the baffle float.


Scheme

top
AV 23 Balancing valves SETTER Rondo
Balancing valve AV 23

AV 23 Balancing valves SETTER Rondo

   Application
Direct regulation and indication of flows to consumers.

   Direct hydraulic balancing and control of flows to consumers. SETTER Rondo balancing valves offer a quick, easy and accurate method of adjusting the flow rates through heating, ventilation, air conditioning and cooling systems.
   Correct balancing of hydraulic circuits allows for lower flow temperatures, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Rondo balancing valves, any expert can set the appropriate water distribution on the premises in question, thus avoiding investments in training and costly measuring devices.

   Installation
   The balancing valve requires a straight section of pipe of the same length and diameter as the system.
   The valve can be installed in a horizontal, vertical or inclined position. Care should be taken in order to ensure that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the displacement principle of a baffle disk, which is inserted in a measuring tube. The movement of the baffle disc is transformed to the sight glass by a mechanical device.
   The scale printed on the sight glass allows the flow rate to be read with ease.
   Turning the sight glass changes the opening profile of the valve and allows the desired flow rate to be set.


Scheme

top
AV 23 Balancing valves SETTER Inline
Balancing valve AV 23 LogoLogo

AV 23 Balancing valves SETTER Inline

   Application
Direct regulation, reading and shut-off of flows in systems.

   Direct hydraulic balancing and control of flows to consumers or in a subsystem. Balancing valves offer a quick, easy and accurate method of adjusting the flow rates through heating, ventilation, air conditioning and cooling systems.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Inline balancing valves, any expert can set the appropriate water distribution on the premises in question, thus avoiding investments in training and costly measuring devices.

   Installation
   The valve can be installed in a horizontal, vertical or inclined position. Care should be taken in order to ensure that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float. The flowmeter is built into the housing.
   The balancing can be carried out with a screwdriver at the adjusting screw. The reading position is the bottom line of the baffle float.


Scheme

top
AV 23 Balancing valves SETTER Inline UN
Balancing valve AV 23

AV 23 Balancing valves SETTER Inline UN

   Application
Direct regulation, indication and isolation of flows in systems.

   Direct hydraulic balancing and control of flows at the intake manifold of circulating pumps. SETTER balancing valves offer an easy and accurate method of adjusting the flow rates through heating, ventilation, air conditioning and cooling systems.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Inline UN balancing valves, any qualified fitter can set the appropriate flow rate on the premises in question, thus avoiding investments in training and costly measuring devices.

   Installation
   The valve can be installed in a horizontal, vertical or inclined position. Care should be taken to ensure that the arrow is pointing in the direction of the flow. The SETTER Inline UN can be built into the 1" threaded pump connection to the intake manifold of the circulating pump thanks to its special housing design.

   Operation
   The flow measurement is based on the principle of a baffle float with return spring.
   The flowmeter is built into the housing. The balancing can be carried out with a screwdriver at the adjusting screw. The reading position is the bottom line of the baffle float.
   Important when using glycol
   The system medium must be allowed to flow through the measuring body for at least 2 hours prior to reading the flow rate when performing the initial start-up or refilling the system.


Scheme

top
AV 23 Balancing valves SETTER Bypass SD
Balancing valve AV 23 SD

AV 23 Balancing valves SETTER Bypass SD

FEMALE THREAD connection

   Application
Direct regulation, indication and isolation of flows in systems.

   Direct hydraulic balancing and control of flows to consumers or in a subsystem. SETTER Bypass balancing valves offer an easy and accurate method of adjusting the flow rates for heating, ventilation, air conditioning and cooling systems.
The solar type is designed for higher operating temperatures.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Bypass SD balancing valves, any qualified fitter can set the appropriate flow rate using the unique flow measurement device, avoiding investments in training and costly measuring devices.

   Installation
   The SETTER Bypass SD requires a straight section of pipe of the same length and diameter as the system. The valve can be installed in a horizontal, vertical or inclined position. Care should be taken that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float with return spring. The reading position is the bottom line of the baffle float.
   The measuring device is placed in a bypass to the main flow, isolated from system flow.
   By demand the bypass, with self locking valves, gets opened / closed by pressing / releasing the clamp. Reading the flow rate has no influence on the main flow rate.


Scheme

top
AV 23 Balancing valves SETTER Bypass SD
Balancing valve AV 23 SD

AV 23 Balancing valves SETTER Bypass SD

MALE THREAD connection

   Application
Direct regulation, indication and isolation of flows in systems.

   Direct hydraulic balancing and control of flows to consumers or in a subsystem. SETTER Bypass balancing valves offer an easy and accurate method of adjusting the flow rates for heating, ventilation, air conditioning and cooling systems.
The solar type is designed for higher operating temperatures.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Bypass SD balancing valves, any qualified fitter can set the appropriate flow rate using the unique flow measurement device, avoiding investments in training and costly measuring devices.

   Installation
   The SETTER Bypass SD requires a straight section of pipe of the same length and diameter as the system. The valve can be installed in a horizontal, vertical or inclined position. Care should be taken that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float with return spring. The reading position is the bottom line of the baffle float.
   The measuring device is placed in a bypass to the main flow, isolated from system flow.
   By demand the bypass, with self locking valves, gets opened / closed by pressing / releasing the clamp. Reading the flow rate has no influence on the main flow rate.


Scheme

top
AV 23 Balancing valves SETTER Bypass HT
Balancing valve AV 23 HT

AV 23 Balancing valves SETTER Bypass HT

Solar type

   Application
Direct regulation, indication and isolation of flows in systems.

   Direct hydraulic balancing and control of flows to consumers or in a subsystem. SETTER Bypass balancing valves offer an easy and accurate method of adjusting the flow rates for heating-, ventilation-, air conditioning - and solar systems. The HT- type is designed for higher operating temperatures.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Bypass SD balancing valves, any qualified fitter can set the appropriate flow rate using the unique flow measurement device, avoiding investments in training and costly measuring devices.

   Installation
   The SETTER Bypass SD requires a straight section of pipe of the same length and diameter as the system.
   The valve can be installed in a horizontal, vertical or inclined position. Care should be taken that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float with return spring. The reading position is the bottom line of the baffle float.
   The measuring device is placed in a bypass to the main flow, isolated from system flow.
   By demand the bypass, with self locking valves, gets opened / closed by pressing / releasing the clamp.
   Reading the flow rate has no influence on the main flow rate.


Scheme

top
AV 23 Balancing valves SETTER Bypass (flange)
Balancing valve AV 23 (flange)

AV 23 Balancing valves SETTER Bypass (flange)

   Application
Direct regulation, reading and shut-off of flows in systems.

   Direct hydraulic balancing and control of flows to consumers or in a subsystem. Balancing valves offer a quick, easy and accurate method of adjusting the flow rates through heating, ventilation, air conditioning and cooling systems.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With SETTER Bypass balancing valves, any expert can set the appropriate water distribution on the premises in question, thus avoiding investments in training and costly measuring devices.

   Installation
   The balancing valve requires a straight section of pipe of the same length and diameter as the system. The valve can be installed in a horizontal, vertical or inclined position. Care should be taken in order to ensure that the arrow is pointing in the direction of the flow.

   Operation
   The flow measurement is based on the principle of a baffle float. The flowmeter is flange-mounted to the side of the housing. Two check valves separate the measuring device from the valve body in normal operation. The visual flow indication is only activated when both valves are open. The flow indicated on the measuring device does not change if the check valves are subsequently shut off for operation.


Scheme

top
AO 23 Balancing valves TOPMETER Flow pipe
AO 23 Balancing valves TOPMETER Flow pipe

AO 23 Balancing valves TOPMETER

FLOW PIPE

   Application
Direct regulation, indication and shut-off of flow from heating and cooling circuits.

   Direct hydraulic balancing and control of flows in the flow pipe bar of the manifold. The Topmeter offers an easy and accurate method of adjusting the flow rates in heating and cooling circuits. Thanks to intensive development work and new technologies, the Topmeter can be integrated efficiently in the flow pipe bar to ensure reliable indicator values.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With the Topmeter, any qualified fitter can set the appropriate flow rate on the premises in question, thus avoiding investments in training and expensive measuring devices.

   Installation
   The Topmeter is installed in the flow pipe bar of the manifold in a horizontal or vertical position. The manifold must be adapted to comply with the manufacturer's specifications and to exclude the possibility of error tolerances.

   Operation
   The flow measurement is based on the displacement principle of a baffle disc, which is inserted in a measuring tube. The position is conveyed to the sight glass by means of a sliding bar, which fixes the baffle disc to the indicator unit. The scale printed on the sight glass allows the flow rate to be read with ease.    Turning the black spindle changes the opening profile of the valve and allows the desired flow rate to be set. The flow is isolated by turning the wheel fully.


Scheme
AO 23 Balancing valves TOPMETER Return pipe
AO 23 Balancing valves TOPMETER Return pipe

AO 23 Balncing valves TOPMETER

RETURN PIPE

   Application
Direct regulation, indication and isolation of flows from heating and cooling circuits in manifold return pipe bars.

   The Topmeter offers an easy and accurate method of adjusting flow rates. The underlying measuring principle requires that the flow has settled in order to ensure reliable indicator values. No complicated flow adjustment is required on the return pipe Topmeter to achieve this. Rather, the medium allows ideal inflow from the upstream inlet pipe.
   Correct balancing of hydraulic circuits ensures optimum energy distribution, resulting in more efficient and economical operation in accordance with the energy saving regulations provided for by legislation.
   With the Topmeter, any qualified fitter can set the appropriate flow rate on the premises in question, thus avoiding investments in training and expensive measuring devices.

   Installation
   The Topmeter is installed in the return pipe bar of the manifold in a horizontal or vertical position. The manifold setting must be adapted to comply with the manufacturer’s specifications to ensure efficient operation.

   Operation
   The flow measurement is based on the displacement principle of a baffle disc, which is inserted in a measuring tube. The position is conveyed to the sight glass by means of a sliding bar, which fixes the baffle disc to the indicator unit. The scale printed on the sight glass allows the flow rate to be read with ease.    Turning the black spindle changes the opening profile of the valve and allows the desired flow rate to be set. The flow is isolated by turning the spindle fully.